Free HVAC calculator

Subcooling calculator

This subcooling calculator takes the liquid line pressure and the liquid line temperature and returns the subcooling: the condenser saturation temperature minus the liquid line temperature, read from a published pressure temperature chart for R-410A, R-454B, R-32 or R-22. Compare it with the subcooling on the unit's data plate.

Use the refrigerant on the unit's nameplate.

psig

High side gauge at the liquid service port.

°F

Clamp probe on the liquid line near the outdoor unit.

Formula: subcooling = condenser saturation temperature at the liquid pressure minus the liquid line temperature.

Compare the answer with the target on the unit's data plate or the manufacturer's charging chart, not a number from the internet.

R-410A subcooling

10.1°F

90.0°F on the line against 100.1°F saturation at 319.0 psig.

Condenser saturation temperature
100.1°F
Liquid line temperature
90.0°F
Subcooling
10.1°F
PT chart point used
Bubble point (liquid column)

PT chart

Liquid side PT chart

Saturation pressure in psig at condensing temperatures. The blends use the liquid (bubble) column.

Liquid side pressure temperature chart, psig, for R-410A, R-454B, R-32 and R-22
Saturation tempR-410A liquidR-454B liquidR-32R-22
80°F236.5225.6241.5143.6
84°F251.6239.9256.9153.2
88°F267.3254.8273.0163.2
92°F283.6270.4289.8173.7
96°F300.7286.6307.4184.6
100°F318.6303.6325.7195.9
105°F341.9325.7349.6210.8
110°F366.4348.9374.9226.4
115°F392.3373.4401.4242.8
120°F419.4399.1429.3260.0
125°F447.9426.0458.7278.0
130°F477.9454.2489.5296.9

How it works

How to calculate subcooling

1. Let it run.Run the system in cooling mode for at least 15 minutes before you check the charge, as Bryant's procedure asks.

2. Read the liquid side. Take the pressure at the liquid service port and the liquid line temperature near the outdoor coil.

3. Look up saturation. The subcooling calculator finds the pressure on the chart for the refrigerant you picked and reads the condensing temperature, interpolating in a straight line between rows. For R-410A and R-454B it reads the liquid (bubble) column.

4. Subtract. Saturation temperature minus liquid line temperature is the subcooling. A negative answer means the line reads warmer than saturation, so check the gauge, the probe and the refrigerant first.

5. Compare with the data plate. Subcooling is the charging guide on TXV systems; on a fixed orifice system use the superheat calculator and the unit's superheat table. If you are checking whether the system was sized right in the first place, the AC tonnage calculator gives a rule of thumb figure.

Questions

What HVAC techs ask about this

How do you calculate subcooling?
Read the liquid line pressure, look up the refrigerant's saturation temperature at that pressure on a PT chart, and subtract the liquid line temperature from it. R-410A liquid at 318.6 psig saturates at 100°F, so a 90°F liquid line has 10°F of subcooling.
What should subcooling be?
The required subcooling is set by the manufacturer for that unit. Bryant's charging method sends you to the unit rating plate or service manual for it, and allows a tolerance of plus or minus 3°F. Use the number on the data plate of the unit you are working on.
Where do I take the liquid line readings?
In Bryant's method: the pressure at the liquid service valve with an accurate gauge, and the temperature on the liquid line near the outdoor coil with a thermistor or electronic thermometer, after at least 15 minutes of running in cooling mode.
Is subcooling too low a sign to add refrigerant?
In Bryant's subcooling method, if the liquid line is warmer than the required temperature you add refrigerant, and if it is cooler you remove refrigerant. Follow the procedure in the installation instructions for the unit you are charging.
Why does the subcooling calculator use the bubble point?
Subcooling is measured on liquid, so for a blend it uses the liquid (bubble) column of the chart. For R-410A the two columns are within about 1 psig, but for R-454B they are not: at the 100°F liquid pressure of 303.6 psig, the vapor column reads 102.7°F, which would add 2.7°F of false subcooling.
What temperature is R-22 at 196 psig?
About 100°F. The Daikin chart lists R-22 at 195.9 psig for 100°F, and Bryant's subcooling table starts its 196 psig row at 100°F for zero subcooling.

Sources

Where the numbers come from

  1. Daikin Comfort Technologies North America, A1 vs. A2L Pressure Temperature Chart, USA (°F/psig), PM-A2LPTC-USA_04-24, values by Weitron. Every saturation pressure and temperature on this page and in the calculator, with liquid and vapor columns for R-410A and R-454B, and the EPA SNAP note on A2L refrigerants
  2. Bryant / Day & Night, 1997 Piston Guide for Residential Split-Systems, form AP01 02-10. The superheat and subcooling charging methods: superheat for non TXV metering devices, subcooling for TXV units, 15 minutes of running, where to take each reading, the required subcooling from the rating plate

Next step

Get your HVAC company recommended by AI in 90 days.

We run the questions your customers ask ChatGPT and Google AI Mode in your city and show you who gets recommended today. Then we fix the pages, listings and answers that decide it.

$999 a month, 3-month minimum, then month to month. If AI is not recommending you for 3 of your 5 questions by day 90, you get every dollar back.

Book a free AI strategy call

One business per industry per city. Founder led. Dated proof every 2 weeks.