Free HVAC calculator

Superheat calculator

This superheat calculator takes the suction pressure and the suction line temperature and returns the superheat: the line temperature minus the evaporator saturation temperature, read from a published pressure temperature chart for R-410A, R-454B, R-32 or R-22. Check the result against the target on the unit's data plate or charging chart.

Use the refrigerant on the unit's nameplate.

psig

Low side gauge at the suction (vapor) service port.

°F

Clamp probe on the suction line near the service valve, insulated.

Formula: superheat = suction line temperature minus the evaporator saturation temperature at the suction pressure.

Compare the answer with the target on the unit's data plate or the manufacturer's charging chart, not a number from the internet.

R-410A superheat

10.2°F

50.0°F on the line against 39.8°F saturation at 118.0 psig.

Evaporator saturation temperature
39.8°F
Suction line temperature
50.0°F
Superheat
10.2°F
PT chart point used
Dew point (vapor column)

PT chart

Suction side PT chart

Saturation pressure in psig at evaporator temperatures. The blends use the vapor (dew) column.

Suction side pressure temperature chart, psig, for R-410A, R-454B, R-32 and R-22
Saturation tempR-410A vaporR-454B vaporR-32R-22
20°F78.470.980.043.1
24°F85.577.587.347.6
28°F93.184.495.152.4
32°F101.191.8103.257.5
36°F109.599.5111.862.9
40°F118.4107.7121.068.6
44°F127.7116.3130.574.5
48°F137.5125.4140.680.8
52°F147.9134.9151.287.4
56°F158.7144.9162.494.4
60°F170.1155.4174.0101.6

How it works

How to calculate superheat

1. Let it run.Bryant's charging procedure asks for at least 15 minutes of running in cooling mode before you check the charge.

2. Read the suction pressure at the vapor service port, and the suction line temperature with an accurate thermistor or electronic thermometer on the line near the service valve, insulated from the air.

3. Look up saturation. The superheat calculator finds the pressure on the chart for the refrigerant you picked and reads the temperature, interpolating in a straight line between rows. For R-410A and R-454B it reads the vapor (dew) column.

4. Subtract. Suction line temperature minus saturation temperature is the superheat. A negative answer means a reading is off, so check the gauge, the probe and the refrigerant before you touch the charge.

5. Compare with the target.The target comes from the manufacturer. On a fixed orifice system it depends on the outdoor dry bulb and the indoor wet bulb, read from the unit's charging table. On a TXV system charge by subcooling instead, with the subcooling calculator. Sizing a new system first? Start with the AC tonnage calculator.

Questions

What HVAC techs ask about this

How do you calculate superheat?
Read the suction pressure, look up the refrigerant's saturation temperature at that pressure on a PT chart, and subtract it from the suction line temperature. R-410A at 118.4 psig saturates at 40°F, so a 50°F suction line has 10°F of superheat.
What should superheat be?
Whatever the unit's charging chart says for the conditions you measured. On fixed orifice (piston) systems the target superheat changes with the outdoor dry bulb and the indoor wet bulb, so the manufacturer prints a table on the unit or in its installation instructions. Use that, not a single number.
Superheat or subcooling: which one do I charge by?
Bryant's piston guide puts it simply: for non TXV metering devices superheat is the guide, and for units with a TXV subcooling is the guide, both in cooling mode. Follow the installation instructions for the unit in front of you.
What temperature is R-410A at 118 psig?
About 40°F. The Daikin chart lists R-410A vapor at 118.4 psig for 40°F and 113.9 psig for 38°F, so 118 psig reads 39.8°F.
Why does the superheat calculator use the dew point for R-454B?
R-454B is a blend, so it boils over a small temperature range. The chart gives a liquid and a vapor pressure for each temperature, and superheat is measured on vapor, so it uses the vapor (dew) column. Reading the liquid column instead at the 40°F dew pressure gives 37.4°F, a 2.6°F error in the superheat.
Can I use the R-410A numbers on an R-32 or R-454B system?
No. Each refrigerant has its own PT column: at 40°F, R-410A vapor is 118.4 psig, R-32 is 121.0 psig and R-454B vapor is 107.7 psig. The Daikin chart also notes that, under current EPA SNAP approvals, A2L refrigerants go only in new equipment, so always use the refrigerant on the nameplate.

Sources

Where the numbers come from

  1. Daikin Comfort Technologies North America, A1 vs. A2L Pressure Temperature Chart, USA (°F/psig), PM-A2LPTC-USA_04-24, values by Weitron. Every saturation pressure and temperature on this page and in the calculator, with liquid and vapor columns for R-410A and R-454B, and the EPA SNAP note on A2L refrigerants
  2. Bryant / Day & Night, 1997 Piston Guide for Residential Split-Systems, form AP01 02-10. The superheat and subcooling charging methods: superheat for non TXV metering devices, subcooling for TXV units, 15 minutes of running, where to take each reading, the required subcooling from the rating plate

Next step

Get your HVAC company recommended by AI in 90 days.

We run the questions your customers ask ChatGPT and Google AI Mode in your city and show you who gets recommended today. Then we fix the pages, listings and answers that decide it.

$999 a month, 3-month minimum, then month to month. If AI is not recommending you for 3 of your 5 questions by day 90, you get every dollar back.

Book a free AI strategy call

One business per industry per city. Founder led. Dated proof every 2 weeks.